4 - 51
4.5 Remote Operation Function
4.5.4 Relation between remote operation and RUN/STOP status
4
FUNCTIONS
4.5.4 Relation between remote operation and RUN/STOP status
This section explains the operations resulting from the combinations of the remote
operation and the RUN/STOP/MODE switch setting of the C Controller module.
(1) Relation between remote operation and RUN/STOP status of C
Controller module
The following table indicates the operations resulting from the combinations of the
remote operation and the RUN/STOP status of the C Controller module.
* 1 It is necessary to set "Remote reset" to "Allow" on the <<System setting>> tab of the C Controller
setting utility.
* 2 Resetting is executable when the C Controller module, whose RUN/STOP/MODE switch is set to
RUN, has been placed in the STOP status by remote STOP.
* 3 Including the case where the C Controller module is stopped due to an error.
(2) Remote operations from the same development environment (personal
computer) or user program
When more than one remote operation is attempted from the same development
environment (personal computer) or the same user program, the status caused by
later remote operation becomes effective.
(3) Remote operation from multiple development environments (personal
computers) or user programs
Remote operation can be performed for the C Controller module where another
remote operation has already been executed from a different development
environment (personal computer) or user program.
(4) Remote operation from the C Controller module toward CPU No.1
(programmable controller CPU)
Remote operations are not executable from the C Controller module when remote
operation is executed to the CPU No.1 from the other peripheral devices (such as GX
Developer).
Execute remote RUN and cancel remote operation of the peripheral device where
remote operation is being performed.
For example, when remote PAUSE is executed in the other peripheral device, the
PAUSE status of the CPU No.1 will not change even if executing remote operation
from the C Controller module.
When executing remote RUN in the peripheral device where remote PAUSE is being
executed and canceling remote operation, remote operation from the C Controller
module can be executed.
Table4.16 Relation between RUN/STOP status and remote operation
RUN/STOP/MODE switch
Remote operation
RUN STOP PAUSE
RESET
*1
RUN RUN STOP PAUSE *2
STOP STOP STOP STOP
RESET
*3