3 - 1
3.1 General Specifications
3
SPECIFICATIONS
CHAPTER3 SPECIFICATIONS
3.1 General Specifications
The following indicates the general specifications of the C Controller module.
* 1 This indicates the section of the power supply to which the equipment is assumed to be
connected between the public electrical power distribution network and the machinery within
premises. Category II applies to equipment for which electrical power is supplied from fixed
facilities.
The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
* 2 This index indicates the degree to which conductive material is generated in terms of the
environment in which the equipment is used.
Pollution level 2 is rated when only non-conductive pollution occurs. A temporary conductivity
caused by condensing can be expected occasionally.
* 3 The storage ambient temperature is -20 to 75 if the system includes the AnS series modules.
* 4 The operating ambient humidity and storage ambient humidity are 10 to 90%RH if the system
includes the AnS series modules.
* 5 Do not use or store the C Controller module under pressure higher than the atmospheric pressure
of altitude 0m.
Doing so can cause a malfunction.
For use in a pressurized environment, please contact your sales representative.
* 6 When installing a commercially available CompactFlash card into the C Controller module, please
follow the lower specifications of either the C Controller module or CompactFlash card.
Table3.1 General specifications
Item
Specifications
*6
Operating ambient
temperature
0 to 55
Storage ambient
temperature
-25 to 75
*3
Operating ambient
humidity
5 to 95%RH
*4
, non-condensing
Storage ambient
humidity
5 to 95%RH
*4
, non-condensing
Vibration resistance
Conforming
to
JIS B 3502,
IEC 61131-2
Frequency Acceleration Amplitude Sweep count
Under
intermittent
vibration
10 to 57Hz ----
0.075mm
(0.003inch)
10 times each
in X, Y, Z
directions
(for 80 min.)
57 to 150Hz
9.8m/s
2
----
Under
continuous
vibration
10 to 57Hz ----
0.035mm
(0.001inch)
57 to 150Hz
4.9m/s
2
----
Shock resistance
Conforming to JIS B 3502, IEC 61131-2 (147 m/s
2
, 3 times in each of 3 directions X, Y, Z)
Operating ambience No corrosive gases
Operating altitude
*5
2000m (6562ft.) max.
Installation location Inside control panel
Overvoltage
category
*1
II max.
Pollution level
*2
2 max.