6
I/O NUMBER ASSIGNMENT
6.5 I/O Number Assignment
6.5.1 I/O number of base unit
6 - 14
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
FUNCTIONS
5
SETTING AND
PROCEDURES
6
I/O NUMBER
ASSIGNMENT
7
MEMORIES AND
FILES
8
INSTALLING /
UNINSTALLING
6.5 I/O Number Assignment
6.5.1 I/O number of base unit
The C Controller module assigns I/O numbers at power-on or reset.
Figure 6.14 shows an example of the I/O number assignment when the base unit is set in
Auto mode without I/O assignment.
The above example assumes that the I/O points of the intelligent function module are 32
points.
The number of I/O points changes depending on the intelligent function module.
Check the number of I/O points in the manual of the used intelligent function module
before assignment.
POINT
The C Controller module can control the system even if I/O numbers have not
been assigned on the C Controller setting utility.
Figure 6.14 I/O number assignment example
CPU
Q35B (5 slots occupied)
Empty slot points set on the <<System
setting>> tab of the C Controller setting
utility. (Default: 16 points)
Q65B (5 slots occupied)
Q65B (8 slots occupied)
Extension cableExtension cable
X00 to X0F
90 to AF
B0 to CF
D0 to EF
YF0 to YFF
X10 to X1F
X20 to X3F
X40 to X4F
X50 to X8F
012 34
567 89
10 11 12 13 14 15 16 17
X110 to X11F
X120 to X12F
130 to X14F
150 to X16F
170 to X18F
Y190 to Y19F
Y1A0 to Y1AF
Y1B0 to Y1BF
Empty (100 to 10F)
The slot numbers next to the
last slot number of the main
base unit are assigned to the
1st extension base unit .
The slot numbers next to the last
slot number of the 1st stage's
extension base unit are assigned to
the 2nd extension base unit .
Allocate the I/O number with
the I/O points of each slot
0 to F
X 0 to F
Y 0 to F
:
:
:
Input module
Output module
Intelligent function module
I/O number assignment order
Number of I/O points
Slot number
I/O number
Assignment order
Number of slot points
Assignment order
Number of slot points
Assignment order
Number of slot points
16
points
16
points
16
points
16
points
16
points
32
points
32
points
16
points
16
points
16
points
16
points
16
points
32
points
32
points
32
points
32
points
16
points
64
points
Extension 1
Extension 2

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals