12
MULTIPLE CPU SYSTEM CONFIGURATION
12.1 System Configuration
12.1.4 System configuration (When CPU No. 1 is C Controller module)
12 - 7
9
UTILITY OPERATION
10
FUNCTIONS AND
PROGRAMMING
11
OVERVIEW OF
MULTIPLE CPU
SYSTEM
12
MULTIPLE CPU
SYSTEM
CONFIGURATION
13
MULTIPLE CPU
SYSTEM
CONCEPT
14
COMMUNICATIONS
BETWEEN CPU
MODULES
15
PARAMETERS
ADDED FOR
MULTIPLE CPU
16
PRECAUTIONS FOR
USE OF AnS SERIES
MODULE
Precautions
• Do not use extension cable longer than 13.2 m (43.28 feet).
• When using an extension cable, keep it away from the main circuit (high voltage
and large current).
• When setting the number of extension stages, set the number in ascending order
to avoid duplicated setting.
• If the Q5 B and Q6 B extension base units are used in the same system, there
are no restrictions on the connection order of the Q5 B and Q6 B.
However check whether they are applicable or not, referring to the QCPU User's
Manual (Hardware Design, Maintenance and Inspection).
• The QA1S6 B and Q6 RB cannot be used as extension base units.
• Connect an extension cable between the OUT connector of an extension base
unit and the IN connector of another extension base unit.
• When 66 or more modules are mounted, an intelligent function module
assignment error (error code: 2124, SP. UNIT LAY ERR.) occurs. (Including the
CPU module)
• The C Controller module does not allow bus connection of the GOT.
• "No. of CPU" indicates the number of CPU modules set in the "No. of CPUs" on
the <<Multiple CPU setting>> tab of the C Controller setting utility.
• Refer to the Motion CPU manual for details of the Motion CPU.
• When a multiple CPU system is configured using the C Controller module, the
redundant power base unit is not applicable.
Table12.1 Restrictions on System Configuration, Applicable Base Units, Extension Cables, Power Supply Modules
CPU number CPU module 1: CPU No.1, CPU module 2: CPU No.2, CPU module 3: CPU No.3, CPU module 4: CPU No.4
Maximum number of
extension stages
7 extension stages
Maximum number of
mounted I/O modules
No. of CPUs 2 3 4
Number of mounted modules 63 62 61
Available main base
unit model
Q33B, Q35B, Q38B, Q312B
Available extension
base unit model
Type not requiring power supply module Q52B, Q55B
Type requiring Q series power supply module Q63B, Q65B, Q68B, Q612B
Available extension
cable type
QC05B, QC06B, QC12B, QC30B, QC50B, QC100B
Available power
supply module model
Q61P-A1, Q61P-A2, Q61P, Q62P, Q63P, Q64P

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals