5 - 54
5.10 Setting C Controller Module Back to Factory-set State
5
SETTINGS AND PROCEDURES BEFORE OPERATION
(4) Standard ROM formatting method
The following describes the standard ROM formatting method and the operation to be
performed after standard ROM formatting.
If the standard ROM is formatted, each file in the standard ROM is cleared.
Back up the essential data, user program and parameter file before performing the
following operations. ( Section 7.2.1)
(a) Formatting the standard ROM
• Write the following script file "STARTUP.CMD" to the CompactFlash card,
install the CompactFlash card into the C Controller module, and start up the C
Controller module.
(The RUN LED flashes during processing of the script file "STARTUP.CMD".)
* 1 The sample script file for standard ROM formatting is registered to the development
environment (personal computer) after installation of SW PVC-CCPU.
( Section 10.4)
• When the RUN LED stops flashing and the MODE LED is flashing green, it
indicates the completion of standard ROM formatting and shutdown
processing.
Power off the C Controller module.
The ERR LED flashes if the standard ROM formatting and shutdown
processing are abnormally terminated. (In such a case, perform the above
steps again.)
(b) Operation after standard ROM formatting
After standard ROM formatting, data such as various parameters and user
programs have been deleted. (
This section (2))
Therefore, access the C Controller module from the C Controller setting utility
using the default IP address (192.168.3.3), and write the default parameters (or
any desired parameters).
After writing parameters and setting the IP address, reset the C Controller
module.
IMPORTANT
1. Be sure to format the standard ROM by the above method (a).
Do not format it using a command from Shell of Tornado.
2. During standard ROM formatting, do not power off the C Controller system or
reset the C Controller module.
Doing so may disable normal startup of the C Controller module.
<Sample script file for standard ROM formatting
*1
>
STARTUP.CMD
diskFormat("/ROM")
userShutdownRom

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals