MULTIPLE CPU SYSTEM CONFIGURATION
12.1 System Configuration
12.1.6 System configuration (When CPU No.1 is High Performance model QCPU)
12 - 13
9
UTILITY OPERATION
10
FUNCTIONS AND
PROGRAMMING
11
OVERVIEW OF
MULTIPLE CPU
SYSTEM
12
MULTIPLE CPU
SYSTEM
CONFIGURATION
13
MULTIPLE CPU
SYSTEM
CONCEPT
14
COMMUNICATIONS
BETWEEN CPU
MODULES
15
PARAMETERS
ADDED FOR
MULTIPLE CPU
16
PRECAUTIONS FOR
USE OF AnS SERIES
MODULE
Precautions
• Do not use extension cable longer than 13.2 m (43.28 feet).
• When using an extension cable, keep it away from the main circuit (high voltage
and large current).
• When setting the number of extension stages, set the number in ascending order
to avoid duplicated setting.
• If Q5 B / Q6 B and QA1S6 B extension base units are used in the same
system, be sure to connect Q5 B / Q6 B at first and then QA1S6 B.
Make the setting of the stage number of extension base units, starting from
Q5 B / Q6 B in ascending order. Refer to the QCPU User's Manual (Hardware
Design, Maintenance and Inspection) and check if they can be used.
• The QA1S6 B extension base unit can be used only when all of the AnS series
modules are set to be controlled by the same High Performance model QCPU.
• The Q6 RB cannot be connected as an extension base unit.
• Connect an extension cable between the OUT connector of an extension base
unit and the IN connector of another extension base unit.
• When 66 or more modules are mounted, an intelligent function module
assignment error (error code: 2124, SP. UNIT LAY ERR.) occurs. (Including the
CPU module)
• "No. of CPU" indicates the number of CPU modules set in the "No. of CPU" on
the <<Multiple CPU setting>> tab of the C Controller setting utility.
• Refer to the manuals of the corresponding CPU modules for details of the
programmable controller CPU and Motion CPU.
• When a multiple CPU system is configured using the C Controller module, the
redundant power base unit is not applicable.
Table12.5 Restrictions on System Configuration, Applicable Base Units, Extension Cables, Power Supply Modules
CPU number CPU module 1: CPU No.1, CPU module 2: CPU No.2, CPU module 3: CPU No.3, CPU module 4: CPU No.4
Maximum number of
extension stages
7 extension stages
Maximum number of
mounted I/O modules
No. of CPUs 2 3 4
Number of mounted modules 63 62 61
Available main base
unit model
Q33B, Q35B, Q38B, Q312B
Available extension
base unit model
Type not requiring power supply module Q52B, Q55B
Type requiring Q series power supply
module
Q63B, Q65B, Q68B, Q612B
Type requiring AnS series power supply
module
QA1S65B, QA1S68B
Available extension
cable type
QC05B, QC06B, QC12B, QC30B, QC50B, QC100B
Available power
supply module model
Q series power supply module Q61P-A1, Q61P-A2, Q61P, Q62P, Q63P, Q64P
AnS series power supply module A1S61PN, A1S62PN, A1S63P