rated
Rated motor speed
U
DC max
Maximum permissible DC link voltage in converter:
V
DC max
= 820V for mains voltage 380V … 480V3AC
I
rated
Rated motor current
P
rated
Rated motor power
6.4 Quick commissioning
6.4.1 Quick commissioning with DIP switches
Overview
The G115D converters have been designed to allow quick commissioning to be performed using
two sets of DIP switches. The DIP switches are located on the Wiring Module. To access the DIP
switches, you must rst remove the Electronic Module.
Accessing the DIP switches
WARNING
Electric shock caused by dangerous voltages and currents in the active converter
When power is applied to the converter, even when it is not active, dangerous levels of voltage
and current are present in the system.
Before attempting the removal of any components of the system, the following steps should be
taken to ensure that the system is completely safe:
1. Disconnect all mains power supplies (line supply and external 24 V power supply) to the
system.
2. Wait ve minutes to allow all the residual current and voltages to dissipate fully.
3. Check the voltage at the converter connections before removing any component.
Release the retaining screws (6 x M4) for the Electronic Module by using a 3 mm allen key,
and then remove the module, as shown in the gure below:
Commissioning
6.4Quick commissioning
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 113