7.27.4 Blocking protection, leakage protection and dry-running protection
Overview
In applications with fans, pumps or compressors with the ow characteristic, the torque
follows the speed according to a specic characteristic. An insucient torque for fans
indicates that the power transmission from the motor to the load is interrupted. For pumps,
insucient torque can indicate a leakage or dry-running.
Function description
6SHHG>USP@
SVSHHGWKUHVKROG6SHHGWKUHVKROGS
6SHHGWKUHVKROGS
SPD[LPXPVSHHG
7RUTXHWKUHVKROGQRORDGS
7RUTXHWKUHVKROGORZHUS
7RUTXHWKUHVKROGORZHUS
7RUTXHWKUHVKROGORZHUS
%ORFNLQJPRQLWRULQJWKUHVKROGS
%ORFNLQJPRQLWRULQJS
7RUTXH>1P@
'U\UXQQLQJSURWHFWLRQRU
EURNHQEHOW
'U\UXQQLQJSURWHFWLRQRU
EURNHQEHOW
/HDNDJHSXPSV/HDNDJHSXPSV
%ORFNHG%ORFNHG
If the torque and speed lie in the impermissible range longer than time p2192, the converter
reacts as specied in p2181.
For applications with pumps, the converter detects the following states of the driven load:
• Blocked
• Leakage
• Dry running
For applications with fans or compressors, the converter detects the following states of the
driven load:
• Blocked
• Torn belt
The monitoring is not active below speed threshold 1 and above speed threshold 3.
When using the control mode "U/f control" (p1300 < 10), the "Blocking protection" function
becomes active when the current limit is reached.
No-load monitoring (Page327)
Advanced commissioning
7.27Monitoring the driven load
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 331