G115D wall-mounted converter Standby current (mA)
Mains power supply with 24VDCpower supply
Frame size Rated power 380 V, 50 Hz 380 V, 60 Hz 400 V, 50 Hz 400 V, 60 Hz 480 V, 50 Hz 480 V, 60 Hz
FSA 0.37 kWto 1.5 kW 168 195 171 199 189 224
FSB 2.2 kWto 4 kW 204 239 209 246 235 279
FSC 5.5kWto7.5kW 287 338 296 350 339 404
11.1.4 Technical data of braking resistors
Requirements for the minimum resistance of braking resistors
For each frame size, the minimum resistance of braking resistors is required as follows:
Frame size Rated power Minimum resistance of braking resistors
FSA 0.37 kWto 1.5 kW 200 Ω
FSB 2.2 kWto 4 kW 80 Ω
FSC 5.5 kW to 7.5 kW 40 Ω
Technical data of integrated braking resistor
G115D wall-mounted converter Integrated braking resistor
Frame size Rated power Resistance Continuous braking
power
Peak braking power
1)
FSA 0.37kW to1.5kW 350Ω 10W 100W
FSB 2.2kW to4kW 175Ω 10W 100W
FSC 5.5kWto7.5kW 88Ω 20W 200W
1)
Peak braking power at 10% cycle time of a 120s cycle. For the peak braking power at dierent duty
cycles, refer to the following diagram.
%VUZDZDMF<>
#SBLJOHQPXFS
'4"'4#'4"'4#'4"'4#
'4$'4$'4$
<8>
Technical data
11.1Technical data of the G115D wall-mounted converter
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 415