Macro 34, Slave 1 with prole 7.A.5: Converter → control
• p2080[4] = 722.2 State DI2 → AS-i.DI0
• p2080[5] = 722.3 State DI3 → AS-i.DI1
• Serial data transfer CTT2, four bytes cyclically or acyclically via PIV. The
reading and writing of parameters is possible via the PIV. Because data
is transferred bit-by-bit, the read and write process is very slow.
→ AS-i.DI2
• Time signal for the CTT2 transfer to the AS-i master → AS-i.DI3
Cyclic and acyclic communication via CTT2 (Page180)
Further information
For more information about the AS-i system, see the AS-Interface - Introduction and Basics
Manual.
Overview of the manuals (Page588)
7.7.3 Assignment tables
Fixed speeds - Single Slave
Fixed speeds via the motor control bits
AS-i.DO3 AS-i.DO2 AS-i.DO1 AS-i.DO0 Response in the converter
0 0 0 0 OFF1
0 0 0 1 On + xed speed 1 (factory setting: 1500 rpm)
0 0 1 0 On + xed speed 2 (factory setting: -1500 rpm)
0 0 1 1 On + xed speed 3 (factory setting: 300 rpm)
0 1 0 0 On + xed speed 4 (factory setting: 450 rpm)
0 1 0 1 On + xed speed 5 (factory setting: 600 rpm)
0 1 1 0 On + xed speed 6 (factory setting: 750 rpm)
0 1 1 1 On + xed speed 7 (factory setting: 900 rpm)
1 0 0 0 On + xed speed 8 (factory setting: 1050 rpm)
1 0 0 1 On + xed speed 9 (factory setting: 1200 rpm)
1 0 1 0 On + xed speed 10 (factory setting: 1350 rpm)
1 0 1 1 On + xed speed 11 (factory setting: 1500 rpm)
1 1 0 0 On + xed speed 12 (factory setting: 1650 rpm)
1 1 0 1 On + xed speed 13 (factory setting: 1800 rpm)
1 1 1 0 On + xed speed 14 (factory setting: 1950 rpm)
1 1 1 1 Acknowledge fault or OFF2
Advanced commissioning
7.7Drive control via AS-i
SINAMICS G115D Wall Mounted distributed drive
178 Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA