5.12 Connecting the digital inputs and outputs
5.12.1 Interface description - X07/X08/x05
The G115D converter has four digital inputs (DI 0 to DI 3) and two bidirectional digital inputs/
outputs (DIO 24 and DIO 25). Digital inputs DI 0 and DI 1 can be used to connect an HTL encoder
(track A/B). Digital inputs DI 2 and DI 3 can be used for the safety functions. The bidirectional
DI/DO can be parameterized as digital inputs or digital outputs with parameter p0728.
Connector variant
M12 A-coding connector, 5-pin, female
Digital inputs (X07, X08) and bidirectional digital inputs/outputs (X05)
X07 Pin Signal Description
1 1L+ Unswitched 24 V
2 DI1 Digital input 1
3 1M Unswitched 0 V
4 DI0 Digital input 0
5 FE Functional earth
X08 Pin Signal Description
1 1L+ Unswitched 24 V
2 DI3 Digital input 3
3 1M Unswitched 0 V
4 DI2 Digital input 2
5 FE Functional earth
X05 Pin Signal Description
1 2L+ Switched 24 V
2 DIO25 Bidirectional digital output/input 25
3 2M Switched 0 V
4 DIO24 Bidirectional digital output/input 24
5 FE Functional earth
Wiring
5.12Connecting the digital inputs and outputs
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 81