1. Select the screen form for setting the forced checking procedure.
2. Set the monitoring time to a value to match your application.
Requirement: Forced checking procedure (test stop) must be performed at least once
a year.
3. Using this signal, the converter signals that a forced checking procedure (test stop) is
required.
Interconnect this signal with a converter signal of your choice.
You have set the forced checking procedure (test stop) for the Basic Functions.
Parameters
Parameter Description Setting
p9659 SI forced checking procedure timer
[h]
Monitoring time for the forced dormant error de‐
tection.
Factory setting: 8 h
r9660 SI forced checking procedure re‐
maining time
Displays the remaining time until the forced dor‐
mant error detection and testing the safety switch-
o󹪜 signal paths.
r9773.0...31 CO/BO: SI status (processor 1 + pro‐
cessor 2)
Signals for the higher-level control system.
Bit 31: Test stop is required for STO
7.15.2.7 Finalizing online commissioning
Overview
After you 󹪝nish the con󹪝guration of the safety function, proceed through the following
operations to activate the settings.
Precondition
You are online with Startdrive.
Advanced commissioning
7.15Safe Torque O󹪜 (STO) safety function
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 243

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G115D and is the answer not in the manual?

Siemens SINAMICS G115D Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G115D
CategoryDC Drives
LanguageEnglish

Related product manuals