1. Select the screen form for setting the forced checking procedure.
2. Set the monitoring time to a value to match your application.
Requirement: Forced checking procedure (test stop) must be performed at least once
a year.
3. Using this signal, the converter signals that a forced checking procedure (test stop) is
required.
Interconnect this signal with a converter signal of your choice.
You have set the forced checking procedure (test stop) for the Basic Functions.
❒
Parameters
Parameter Description Setting
p9659 SI forced checking procedure timer
[h]
Monitoring time for the forced dormant error de‐
tection.
Factory setting: 8 h
r9660 SI forced checking procedure re‐
maining time
Displays the remaining time until the forced dor‐
mant error detection and testing the safety switch-
o signal paths.
r9773.0...31 CO/BO: SI status (processor 1 + pro‐
cessor 2)
Signals for the higher-level control system.
Bit 31: Test stop is required for STO
7.15.2.7 Finalizing online commissioning
Overview
After you nish the conguration of the safety function, proceed through the following
operations to activate the settings.
Precondition
You are online with Startdrive.
Advanced commissioning
7.15Safe Torque O (STO) safety function
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 243