Three-wire control, method2
W
W
W
67236723
21
(QDEOH2))
5HYHUVLQJ
&ORFNZLVH&RXQWHU
FORFNZLVH
6WRS6WRS
Enable/OFF1:
Enables the motor to be switched on
or switched o
ON:
Switches on the motor
Reversing:
Reverses the motor direction of rota‐
tion
7.4.1 Two-wire control, method 1
W
W
W
67236723
&ORFNZLVH
&RXQWHUFORFNZLVH
5HYHUVLQJ
212))
6SHHGVHWSRLQW
Command "ON/OFF1" switches the motor on and o. The "Reversing" command inverts the
motor direction of rotation.
ON/OFF1 Reversing Function
0 0 OFF1: The motor stops
0 1
1 0 ON: Clockwise motor rotation
1 1 ON: Counter-clockwise motor rotation
Parameters
Select two-wire control, method1
Parameter Description
p0015=60 Macro drive unit
You must carry out quick commissioning in order to set parameter p0015.
Assigning digital inputs DI to the commands:
DI0: ON/OFF1
DI1: Reversing
Advanced commissioning
7.4Controlling clockwise and counter-clockwise rotation via digital inputs
SINAMICS G115D Wall Mounted distributed drive