10.7 Reduced acceptance test after component replacement and
󹪝rmware change
After a component has been replaced or the 󹪝rmware updated, a reduced acceptance test of the
safety functions must be performed.
Measure Reduced acceptance test
Acceptance test Documentation
Replacing the converter with an
identical type
Not required.
Only check the direction of ro‐
tation of the motor.
Supplement the converter data
Log the new checksums
Countersignature
Supplement the hardware ver‐
sion in the converter data.
Replacing the motor with an identi‐
cal pole pair number
No change.
Replace the gearbox with an identi‐
cal ratio
Replacing safety-related I/O devices
(e.g. Emergency Stop switch).
Not required.
Only check the control of the
safety functions a󹪜ected by
the components that have
been replaced.
No change.
Converter 󹪝rmware upgrade. Not required.
Supplement 󹪝rmware version
in the converter data
Log the new checksums
Countersignature.
Corrective maintenance
10.7Reduced acceptance test after component replacement and 󹪝rmware change
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 409

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G115D and is the answer not in the manual?

Siemens SINAMICS G115D Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G115D
CategoryDC Drives
LanguageEnglish

Related product manuals