The distinction between Emergency O󹪜 and Emergency Stop
"Emergency O󹪜" and "Emergency Stop" are commands that minimize di󹪜erent risks in the
machine or plant.
The STO function is suitable for achieving an emergency stop but not an emergency o󹪜.
Risk: Risk of electric shock: Risk of unexpected motion:
Measure to minimize
risk:
Safe switch o󹪜
Switching o󹪜 the electric power supply
for the installation, either completely
or partially.
Safely stop and safely prevent re‐
starting
Stopping or preventing the dangerous
movement
Command: Emergency O󹪜 Emergency Stop
Classic solution: Switch o󹪜 the power supply: Switch o󹪜 the drive power supply:
0
Solution with the STO
safety function inte‐
grated in the drive:
STO is not suitable for safely switching
o󹪜 an electric voltage.
Select STO:
0
It is permissible that you switch o󹪜 the
converter supply voltage as well. How‐
ever, switching o󹪜 the voltage is not
required as a risk-reduction measure‐
ment.
Advanced commissioning
7.15Safe Torque O󹪜 (STO) safety function
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 235

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS G115D and is the answer not in the manual?

Siemens SINAMICS G115D Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS G115D
CategoryDC Drives
LanguageEnglish

Related product manuals