Selecting the number of drive data sets
Parameter p0180 denes the number of drive data sets (1...4).
Parameter Description
p0010=0 Drive commissioning: Ready
p0010=15 Drive commissioning: Data sets
p0180 Drive data set (DDS) number
Copying the drive data sets
Parameter Description
p0819[0] Source drive data set
p0819[1] Target drive data set
p0819[2]=1 Starts the copy operation
Parameters
Parameter Description Setting
p0010 Drive commissioning parameter l‐
ter
Sets the parameter lter to commission a drive.
0: Ready
1: Quick commissioning (factory setting)
15: Data sets
r0051.0...1 CO/BO: Drive data set DDS eective Displays the eective Drive Data Set (DDS).
p0180 Number of Drive data set (DDS) p0180 = 1, 2, 3 or 4
Factory setting: 1
p0819[0…2] Copy drive data set DDS [0] Source Drive Data Set
[1] Target Drive Data Set
[2] 0→1: Starts the copy operation
Factory setting: 0
Advanced commissioning
7.30Switchover between dierent settings
SINAMICS G115D Wall Mounted distributed drive
Operating Instructions, 07/2023, FW V4.7 SP14, A5E52808211A AA 341