Removing functional grounding connections from the converter
Precondition
Switch o the converter power supply before removing the functional grounding.
WARNING
Electric shock as a result of a residual charge in power components
After the power supply has been switched o, it takes up to ve minutes until the capacitors in
the converter have discharged so that the residual charge is at a non-hazardous level.
Therefore, touching the converter immediately after powering o can result in electric shock
due to residual charge in the power components.
• Check the voltage at the converter connections before you remove the functional
grounding.
Procedure
1. Release the retaining screws (6 x M4) for the Electronic Module by using a 3 mm allen key,
and then remove the module.
(OHFWURQLF0RGXOH
:LULQJ0RGXOH
2. Remove the functional grounding screw marked with the symbol from the back side of
the Electronic Module.