(b) When a programmable controller CPU is No.1 in a multiple CPU system
Before executing remote RESET, check the following 1) and 2).
Remote RESET is not executable if the conditions 1) and 2) are not satisfied.
1) Setting required for remote RESET
For CPU No.1, set "Allow" in "Remote reset" in GX Developer. Parameters
must have been written to CPU No.1 (Reset CPU No.1 after writing the
parameters.)
2) Status of CPU No.1
CPU No.1 must be in STOP status by the following operations.
• Set RUN/STOP switch or RUN/STOP/RESET switch to STOP.
• Execute remote STOP from the user program (mdControl function) of the
C Controller module.
POINT
Remote RESET is not executable from the C Controller module when remote
STOP is performed from the other peripheral devices (such as GX Developer).
Cancel remote STOP of the peripheral device where remote STOP is being
performed.
For the remote operations of the programmable controller CPU, refer to the
following manual.
QCPU User's Manual (Function Explanation, Program Fundamentals)