EasyManuals Logo
Home>Mitsubishi>Controller>MELSEC Q Series

Mitsubishi MELSEC Q Series User Manual

Mitsubishi MELSEC Q Series
664 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #510 background imageLoading...
Page #510 background image
13 - 19
13.4 Access Ranges between CPU Modules and Other Modules
13.4.2 Access to non-controlled modules
13
MULTIPLE CPU SYSTEM CONCEPT
2) Output (Y) data are loaded from the modules indicated in Table13.8 that are
mounted on the main base unit and extension base unit.
3) Outputs cannot be loaded from empty slots and remote stations on
MELSECNET/H, CC-Link, etc. controlled by another CPU.
When the ON/OFF output information to remote stations on MELSECNET/H,
CC-Link, etc. is to be used by the C Controller module, read the
programmable controller CPU devices using the MELSEC data link function.
(b) When "Not all CPUs can read all outputs" has been set
The ON/OFF data output from another CPU to output modules and intelligent
function modules cannot be loaded into the host CPU's output (Y) (remains at
OFF.)
Table13.8 Modules from which outputs can be loaded
Type setting on
<<I/O assignment setting>> tab
of C Controller setting utility
Mounted module
None
Output module
I/O composite module
Intelligent function module
Output
I/O mix
Output module
I/O composite module
Intelli. Intelligent function module

Table of Contents

Other manuals for Mitsubishi MELSEC Q Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC Q Series and is the answer not in the manual?

Mitsubishi MELSEC Q Series Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC Q Series
CategoryController
LanguageEnglish

Related product manuals