Note
If you congure the ET 200iSP in STEP 7 with the GSD le, then SIMATIC PDM is required for
parameter assignment!
7.2 ET 200iSP on PROFIBUS as DPV0, S7 DP or DPV1 device
ET 200iSP on PROFIBUS as DPV0, S7 DP or DPV1 device
The ET 200iSP can be operated either as DPV0, S7 DP or as DPV1 device.
The respective higher-level systems must be able to process the required data.
The following table compares the functions.
Table 7-2 Comparison of DPV0, S7 DP and DPV1
Function DPV0
de‐
vice
S7 DP
device
DPV1
device
Comment
Parameter assignment and conguration with
GSD le
X --- X
Conguration and parameter assignment with
HW Cong
X
1
X X
1
Cyclic data exchange X X X
Acyclic data trac (read/write
data record)
• Free access to parameters
on the eld device
• Reassignment of parame‐
ters of the application
process
Class 1 services
(parameter as‐
signment mas‐
ter, e.g. PLC)
--- X X
Class 2 services
(for example, PD/
OP)
X X X
Diagnostics One interrupt can be re‐
ported per diagnostic
frame. With DPV1 and
S7 DP, an interrupt con‐
sists of device diagnos‐
tics accompanied by an
acknowledgment mech‐
anism that does not ex‐
ist for DPV0.
• Identier-related diagnostics:
X X X
• Module status
X X X
• Channel-related diagnostics
X X X
Interrupts
• Diagnostic interrupt
--- X
2
X
• Hardware interrupt
--- X
2
X
• Pull/plug interrupt
--- X X
• Update interrupt
--- --- X
Commissioning and Diagnostics
7.2 ET 200iSP on PROFIBUS as DPV0, S7 DP or DPV1 device
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 159