7.11.3 Conguring the PROFINET connection
Properties
With the PROFINET IO parameters you dene at which address the ET 200iSP distributed I/O
device is addressed at the PROFINET IO.
Requirements
• The network parameters are set in the hardware conguration of the interface module and
are downloaded to the interface module.
• An IO controller with a PROFINET IO system and an ET 200iSP is created.
• The required network address and the subnet mask are known.
• The MAC address of the IM 152-1PN device is known.
• The rules for the conguration of Ethernet interfaces must be observed.
• HW-Cong is open.
Setting the network conguration
1. Select the "IM 152-1PN", right-click it and select "Object properties".
The "Properties - IM 152-1PN" dialog box opens.
2. In the "Nodes in PROFINET IO system" area, click "Ethernet".
The "Properties - Ethernet interface IM 152-1PN" dialog box opens.
3. Enter the IP address in the "IP address" input eld.
4. In the "Subnet" area, mark the "Plant bus" entry and click "OK".
5. In the "Properties – IM 152-1PN" dialog box, click "OK".
For an online connection to the automation system and connected ET 200iSP, you can search for
the station using the MAC address.
Then load the station.
Changing the network conguration
1. Proceed as described for "Set network conguration". If necessary, a STOP of the station/bus
system is required.
7.11.4 Conguring PROFIBUS DP address
Properties
With the PROFIBUS DP address you dene under which address the ET 200iSP distributed I/O
device is addressed at the PROFIBUS RS 485-IS.
Commissioning and Diagnostics
7.11 Commissioning and starting up the ET 200iSP
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 179