3. Analyze the diagnostic message:
Result for PROFINET conguration:
– Identier-related diagnostics: Bit 3 in byte 7 is set -> Slot 2
Result for PROFIBUS conguration:
– Station status 1 (byte 0): Bit 3 is set -> External diagnostics
– Identier-related diagnostics: Bit 3 in byte 7 is set -> Slot 4
– Module status: Byte 16.7 / 16.6: 11
B
-> No module
4. Plug the pulled electronic module back into the terminal module.
Result:
For PROFINET conguration - LEDs on the interface module IM 152-1PN of the ET 200iSP:
– ER: O
– MT: O
– ACT: On
– RN: On
– PS1: On, PS2: O
– LK1 and/or LK2: on (depending on the nodes connected via ber-optic cables)
For PROFIBUS conguration - LEDs on the interface module IM 152-1DP of the ET 200iSP:
– SF: O
– BF: O
– ON: On
– PS1: On, PS2: O
The diagnostic message has been deleted.
3.15 Wire break of NAMUR encoder on digital input module
Procedure
1. Remove the cable from terminal 1 of the rst electronic module 8 DI NAMUR.
2. For PROFINET conguration - LEDs on the interface module IM 152-1PN of the ET 200iSP:
– ER: Flashes
For PROFIBUS conguration - LEDs on the interface module IM 152-1DP of the ET 200iSP:
– SF: Flashes --> diagnostic message is available.
3. Status LEDs on the electronic module 8 DI NAMUR:
– SF: on --> diagnostic message is available.
– 3: o/on
Commissioning guideline
3.15 Wire break of NAMUR encoder on digital input module
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 57