Measuring range for thermocouple type U
Table 14-27 SIMATIC S7 format: Measuring range type U in °C and °F
Type U in °C Units Type U in °F Units Range
Decimal Hexa‐
decimal
Decimal Hexa‐
decimal
> 850.0 32767 7FFF
H
> 1562.0 32767 7FFF
H
Overow
850.0
:
600.1
8500
:
6001
2134
H
:
17771
H
1562.0
1112.1
15620
11121
3D04
H
2B71
H
Overrange
600.0
:
-200.0
2000
:
-2000
1770
H
:
F830
H
1112.0
:
-328.0
11120
:
-3280
2B70
H
:
F330
H
Nominal range
< -200.0 -32768 8000
H
< -328.0 -32768 8000
H
Underow
14.8.4 Output ranges of the analog output modules in S7 format
Introduction
The tables in this section contain the digitized analog values for the measuring ranges of the
analog output modules.
Since the binary representation of the analog values is always the same, these tables only
contain the comparison of the output ranges to the units.
Output ranges for current: 0 to 20 mA, 4 to 20 mA
Table 14-28 SIMATIC S7 format: Output ranges 0 to 20 mA, 4 to 20 mA
Output range
0 to 20 mA
Output range
4 to 20 mA
Units Range
Decimal Hexadecimal
0 0 > 32511 > 7EFF
H
Overow
23.5178 22.8100 32511 7EFF
H
Overrange
: : : :
20.0007 20.0005 27649 6C01
H
20.0000 20.0000 27648 6C00
H
: : : : Nominal range
0 4.0000 0 0
H
0 3.9995 -1 FFFF
H
Underrange
: : : :
0 0 -6912 E500
H
0 0 < -6913 < E4FF
H
Underow
Analog electronic modules
14.8 Representation of analog values
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 385