12.3.9 Temperature unit
Description
With this parameter you set the temperature unit for the temperature sensors and
thermocouples.
Data format "S7 format": Temperature unit "Celsius" or "Fahrenheit" selectable
The temperature unit parameter is used with the 4 AI RTD and 4 AI TC analog electronic modules.
12.3.10 Slot reference junction/reference junction input
Description
You will nd the description in the section "Fundamentals of analog value processing
(Page 386)".
12.4 Installation of ber-optic cables
Introduction
Fiber-optic cables may only be installed by trained and qualied personnel. Always observe the
applicable rules and statutory regulations. The installation must be carried out with meticulous
care, because faulty installations represent the most common source of error. Causes are:
• Kinking of the ber-optic cable due to an insucient bending radius.
• Crushing of the cable as a result of excess forces caused by persons treading on the cable, or
by pinching, or by the load of other heavy cables.
• Overstretching due to high tensile forces.
• Damage on sharp edges etc.
Local quality assurance
Check the points outlined below before you install the ber-optic cables:
• Does the delivered package contain the correct ber-optic cables?
• Any visible transport damage to the product?
Network interface module
12.4 Installation of ber-optic cables
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 291