8.2 Pulling and plugging electronic modules during operation (hot
swapping)
Properties
The ET 200iSP distributed I/O device supports the removing and inserting of an electronic
module (1 gap) during operation (RUN mode).
When an electronic module is removed the ET 200iSP remains in the RUN mode.
If you have pulled more than one electronic module, then this leads to a station failure of the
ET 200iSP. After you have plugged in all electronic modules again, you must perform a restart
of the ET 200iSP, i.e. switch the supply voltage on and o󹪜 at the power supply module PS.
If you con󹪝gure a ET 200iSP with only one electronic module, then pulling this electronic
module will lead to a station failure of the ET 200iSP. When the electronic module is plugged
in, the ET 200iSP starts up again.
Maintenance
8.2 Pulling and plugging electronic modules during operation (hot swapping)
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 227

Table of Contents

Other manuals for Siemens SIMATIC ET 200iSP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200iSP and is the answer not in the manual?

Siemens SIMATIC ET 200iSP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200iSP
CategoryI/O Systems
LanguageEnglish

Related product manuals