The 󹪝les with the current (new) 󹪝rmware version are available in the 󹪝le system of your PG/
PC.
You have selected the header.upd 󹪝le.
Updating 󹪝rmware via network connection
For information on the procedure, see the STEP 7 online help.
Restarting following an update
The following setting options are available via the "Update 󹪝rmware after download" parameter
to restart after updating the interface module:
"Update 󹪝rmware after download" enabled:
When the update is completed successfully, a reset of the IM 152-1DP is performed
automatically. The module restarts with the newly loaded 󹪝rmware.
CAUTION
STOP of CPU possible
If the "Update 󹪝rmware after download" 󹪝eld is selected, the ET 200iSP station will be
brie󹪞y interrupted. If you have not made any provisions for this situation, the update will
cause to CPU to go to STOP mode due to a rack failure.
"Update 󹪝rmware after download" disabled:
If the update is completed successfully, the IM 152-1DP continues to run with the 󹪝rmware
loaded before the update.
The newly loaded 󹪝rmware is only restarted after the supply voltage is temporarily not
available.
For redundant systems, the "Update 󹪝rmware after download" parameter cannot be disabled.
Bad update
If the update fails, the IM 152-1DP starts up with the ("old") 󹪝rmware that was active before the
update after the supply voltage is switched o󹪜/on. See table Status and error LEDs on the IM
152-1DP in the section Status and error LEDs on the IM 152-1DP (Page 173).
8.9 Reading service data
Properties
The service data contains special information about the status of an ET 200iSP station for
diagnostic purposes.
If you want to transfer the service data of your system to the customer support in case of service,
you have to consider the following:
Maintenance
8.9 Reading service data
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 235

Table of Contents

Other manuals for Siemens SIMATIC ET 200iSP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200iSP and is the answer not in the manual?

Siemens SIMATIC ET 200iSP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200iSP
CategoryI/O Systems
LanguageEnglish

Related product manuals