8.7 Firmware update of the IM 152-1PN
Properties
After (compatible) function extensions, security updates or performance improvements, you
should upgrade (update) the interface module to the latest 󹪝rmware version.
You can obtain the most recent 󹪝rmware versions from your Siemens representative, or
download it from the Internet at: http://www.siemens.com/automation/service&support
(
https://www.siemens.com/automation/service&support)
Tip:
Before updating, note down the current version of your 󹪝rmware. You can read out the
version with HW Con󹪝g.
If you encounter problems with the new 󹪝rmware, you can also download the previous
(current) 󹪝rmware from the Internet and transfer it to the interface module again.
The 󹪝rmware update is performed by the PG/PC via network using the CPU.
Requirements
NOTICE
Requirements for the 󹪝rmware update of the fail-safe electronic modules
The F-CPU must be in the "STOP" operating state.
The supply voltage of the respective fail-safe electronic module is connected.
Note
Updating electronic modules in IO redundancy
If the 󹪝rmware of two redundantly operating electronic modules is to be changed, note the
following:
The update of the second electronic module must not be started until the electronic module that
was updated 󹪝rst is fully operational again.
Readiness for operation is displayed in the input address space on a channel-speci󹪝c basis (value
status QI = good).
You are familiar with the general procedure for updating the 󹪝rmware.
A connection to the IO device is possible.
The storage location of the 󹪝le for the 󹪝rmware update is known.
The engineering system is open.
Procedure
1. Open the hardware con󹪝guration.
2. Select the electronic module in the device view.
3. In the shortcut menu, select the "Online & Diagnostics" menu command.
Maintenance
8.7 Firmware update of the IM 152-1PN
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 233

Table of Contents

Other manuals for Siemens SIMATIC ET 200iSP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200iSP and is the answer not in the manual?

Siemens SIMATIC ET 200iSP Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200iSP
CategoryI/O Systems
LanguageEnglish

Related product manuals