9.4 Mechanical and climatic environmental conditions
Operating conditions
The ET 200iSP is intended for weather-protected, stationary use. The operating conditions
exceed requirements according to DIN IEC 60721-3-3:
• Class 3M3 (mechanical requirements)
• Class 3K3 (climatic requirements)
Climatic environmental conditions
The following climatic environmental conditions apply:
Environmental conditions Areas of application Remarks
Temperature from -20 to 70 °C
1 2
For horizontal installation
from -20 to 50 °C
1 2
For all other mounting positions
Temperature change 10 K/h -
Relative humidity from 5 to max. 95 % Without condensation
Barometric pressure from 1080 to 795 hPa corresponds to a height of
-1000 to 2000 m
Concentration of pollutants SO
2
: < 0,5 ppm;
rel. humidity < 60 %, no condensation
H
2
S: < 0.1 ppm;
rel. humidity < 60 %, no condensation
Test:
10 ppm; 4 days
1 ppm; 4 days
ISA-S71.04 severity level G1; G2; G3 -
1
Output current of the power supply PS DC24V (6ES7138-7EA01-0AA0): Power supply PS 24 VDC (Page 269)
2
Power supply output current PS AC120/230V (6ES7138-7EC00-0AA0): Power supply PS 120/230 VAC (Page 272)
Mechanical environmental conditions
The table below shows the mechanical environmental conditions in the form of sinusoidal
oscillations.
Frequency band Continuous Infrequently
5 ≤ f ≤ 9 Hz 1.75 mm amplitude 3.5 mm amplitude
9 ≤ f ≤ 150 Hz 0.5 g constant acceleration 1 g constant acceleration
General technical specications
9.4 Mechanical and climatic environmental conditions
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK 245