Observing minimum bending radius requirements
Cables must be able to move without constraint, especially in the bending radii of the chain.
Observe the specified minimum bending radii.
Make sure that cables in the drag chain are unattached and movable.
Place the cable fixture in a "dead" zone at each end, suitably far away from each end point of the moving parts.
System connection
Third-party motors that can be operated
You can operate standard asynchronous motors from other manufacturers with the inverter:
Motor damage due to the use of an unsuitable third-party motor
A higher load occurs on the motor insulation in inverter mode than with mains operation. Damage to the motor winding may
occur as a result.
•
Please observe the notes in the System Manual "Requirements for third-party motors"
Additional information is provided on the Internet: Requirements for third-party motors
(https://support.industry.siemens.com/cs/ww/en/view/79690594)
Damage to the control system
The high-voltage components have strong interference on 24 VDC power supplies.
If the 24 VDC power supply is not isolated from high-voltage components, the control system may be damaged.
The 24 VDC protective extra-low voltage
be generated as a protective extra-low voltage with safe electrical isolation
(according to IEC 204-1, Section 6.4, PELV), and grounded by with a PELV M signal connection to the central grounding
point of the system.