User manual of EC160 elevator intelligent integrated machine Function parameters
123
The time from output brake to braking shifting.
Function
code
Instruction Setting range【default value】 Remarks
T0_16 Keeping time of opening delay 0~500.0s【30.0】
Not modify
in running
Press the opening delay button, and the system will close the door automatically after the set
time. Press closing button can close the door in advance.
Enable the function after parameter setting. The parameters are forced
to adjust automatically as follows:
F0_07=1, DOD in the car (same as IND) for the opening delay button;
F0_15=1x, DOD at the car top for the opening delay light.
Function
code
Instruction Setting range【default value】 Remarks
T0_17 Entire running protection time 0~100s【45】
Not modify
in running
This parameter is used to limit the running time of the motor. The elevator will stop immediately
when the time is arrived.
Function
code
Instruction Setting range【default value】 Remarks
T0_18
Single floor running protection
time
0~100s【45】
Not modify
in running
This parameter is used to set the single floor running protection time for the higher floors.
Function
code
Instruction Setting range【default value】 Remarks
T0_19 Fast arrival opening delay 0~65535【0】
Not modify
in running
This parameter is the time from switching on output to opening output at stop of the elevator, unit:
100ms. Generally, it does not need setting.