User manual of EC160 elevator intelligent integrated machine Function parameters
126
If energy saving is necessary in the state, set the closed signal to
normally closed attribute.
Function
code
Instruction Setting range【default value】 Remarks
F0_02 Closing output delay 0~600.0s【0.5】
Not modify
in running
0: do not output closing signal after the door is closed
0.1-600.0 is the closing keeping time after the door is closed (after setting it to 600s, keep closed)
Function
code
Instruction Setting range【default value】 Remarks
F0_03 Fire safety mode 0~3【0】
Not modify
in running
0: China fire safety
1: Australia fire safety
2: Britain fire safety
3: Special function for fire safety 2012
Britain fire safety is also applicable in Hongkong. Enter the fire safety
mode by IND.
As for special function for fire safety 2012, output alarm and low speed
opening by Y5 and Y6, or output by F0_15 mapping onto car board
DOD and PAS light.
Function
code
Instruction Setting range【default value】 Remarks
F0_04
Closing output condition of dual
doors
0~1【0】
Not modify
in running
0: dual door output closing signal when the door lock is blocked
1: end the closing command after the door closed
Set F0-02 to non-zero when selecting dual door output closing signal.
F0-02 closing output delay when selecting to end the closing command
after the door closed.