User manual of EC160 elevator intelligent integrated machine Debugging at fast speed
157
The high speed counting is in reverse direction. When the elevator
goes up, the current height reduces. Please make adjustment
according to the precautions of the master in autotuning;
The number of light panels in door area and the total floors have
position deviation or different setting. Please check whether the signals
from door area is consistent with the total floors;
Down low speed forced deceleration switch does not reset or is offline;
Up low speed forced deceleration switch adhesion or installed too high;
Due to each adjustment on the deceleration switch, redo the hoistway
autotuning.
8.6 Run at fast speed
Avoid terminal landing running in first running at fast speed.
Ensure the protection switches in safety circuit are correct and reliable.
Ensure there is no short circuit of the car and hall lock and the locks can
work normally.
Ensure the forced deceleration switches and limit switch at slow speed
can work normally.
Ensure the hoistway autotuning are succeeded. And the logic setting of
the main board and car main controller is correct.
The elevator runs at slow speed to the leveling of the terminal landing.
Correct the floor displaying and inspect normally. The elevator will open
and close the door automatically to ensure the outside/inside calling
communication is normal.
Run at fast speed in the engine room after the hoistway autotuning, and monitor the feedback
speed on the manual controller.
1. Check nobody is in the car, car top or pit and the doors of the hall and car are closed. Ensure the
safety circuit and door lock circuit are normal.
2. Slowly run the elevator in the engine room to the medium floor, then change into automatic state.
If register single-deck command in the controller, the elevator will run at single-deck speed. Inspect
feedback speed, leveling signal and tractor to check if working normally; if not, adjust relative
parameters.
3. After proper single-deck running, register double-deck command and make the elevator run at
double-deck speed to check whether in normal state.
4. After proper double-deck running, register multi-deck command to check whether in normal