Note: Elevator A 10 floors above ground and 2 floors underground; elevator B 10 floors above
ground and 1 floor underground; elevator C 11 floors above ground and no floor underground.
9.4.10.1 Precautions for EC160 parameters setting
Elevator A: L0_00 (group number) =03; L0_02 (down bias floor) =02; L0_01 (up bias floor) =00;
Elevator B: L0_00 (group number) =04; L0_02 (down bias floor) =01; L0_01 (up bias floor) =00;
Elevator C: L0_00 (group number) =05; L0_02 (down bias floor) =00; L0_01 (up bias floor) =00;
Note: L0_01=00 needs no setting for three elevators;
The group control system can calculate the up bias floor of elevator C according to down bias
floors and total floors.
9.4.10.2 Precautions for MC-GCL parameters setting
In need of separate standby, elevator A stops at the 1
st
floor, elevator B at the 5
th
floor, and elevator
C at the 10
th
floor. The parameters settings are as follows:
Elevator A: P1_00 (down home landing)=03 (set according to the address of the actual floor);
P2_03 (time threshold of separate standby) ≠0 valid;
Elevator B: P1_00 (down home landing)=06 (set according to the address of the actual floor);
P2-_03 (time threshold of separate standby) ≠0 valid;
Elevator C: P1_00 (down home landing)=10 (set according to the address of the actual floor);
P2_03 (time threshold of separate standby) ≠0 valid.
9.5 Instruction of EC-RDB
EC-RDB which adopts four safety relays with highly reliable design has passed the certification of
the elevator safety circuit test.
9.5.1 Installation dimension
Figure 9-12 Installation dimension of EC-RDB