User manual of EC160 elevator intelligent integrated machine Debugging at fast speed
163
autotuning?
[Y] [N]
Load 08.2V
After the autotuning succeeded, set P4_25, P4_26 and P4_27 to start compensation adjustment.
Set P4_25 to the analog voltage when the load of the elevator is balanced. For example, when the
load of the elevator is balanced, the analog voltage in drive monitoring is 4V and thus the value
need to be 40.0%;
When the drive is in the electromotion state, adjust P4_26. Increase compensation if not enough
and decrease it if too high.
When the drive is in the power generation state, adjust P4_27. Increase compensation if not
enough and decrease it if too high.