User manual of EC160 elevator intelligent integrated machine Complete product description
190
P3_18 Zoning mode 2 end time 00.00~23.59【00.00】
P3_19 Mode 2 floor setting-16 00000~65535【00000】
P3_20 Mode 2 floor setting-32 00000~65535【00000】
P3_21 Mode 2 floor setting-48 00000~65535【00000】
P3_22 Mode 2 floor setting-64 00000~65535【00000】
P3_23 Zoning mode 3 enabling 000~127【0】
P3_24
Zoning mode 3 start
time
00.00~23.59【00.00】
P3_25 Zoning mode 3 end time 00.00~23.59【00.00】
P3_26 Mode 3 floor setting-16 00000~65535【00000】
P3_27 Mode 3 floor setting-32 00000~65535【00000】
P3_28 Mode 3 floor setting-48 00000~65535【00000】
P3_29 Mode 3 floor setting-64 00000~65535【00000】
P3_30 MF input setting 1
0: None
1: Up rush hour
2: Down rush hour
3: Zoning mode 1
4: Zoning mode 2
5: Zoning mode 3
P3_31 MF input setting 2
0: None
1: Up rush hour
2: Down rush hour
3: Zoning mode 1
4: Zoning mode 2
5: Zoning mode 3
P3_32 MF input setting 3
0: None
1: Up rush hour
2: Down rush hour
3: Zoning mode 1
4: Zoning mode 2
5: Zoning mode 3
P3_33 MF input setting 4
0: None
1: Up rush hour
2: Down rush hour
3: Zoning mode 1
4: Zoning mode 2
5: Zoning mode 3
P3_34 Customized 00000~65535【00000】
P3_35 Customized 00000~65535【1】
9.4.9.9 Data management
【main menu】
A system control
B fault record
C language selection
【data management】
[1] data saving of the
controller
[2] restore to the factory