80209C_MHW_850-1650-1850_02-2020_ENG_pag. 76
4.8.1. PR.NUM
Acronym Scrolling message Submenu Attributes
PR.NUM PROGRAMMER ACTUAL PROGRAM PR.STP R W
This parameter shows and sets the program number that you intend to modify. Appears only if “Simplified Programmer”
mode is selected - parameter S.PROG = ON).
Unit of measurement: Program number
Options: 1...12
4.8.2. PR.ST.N - Programming step
Acronym Scrolling message Submenu Attributes
PR.ST.N PROGRAMMER ACTUAL STEP PR.STP R W
The parameter shows and sets the number of the programming step being configured. Appears only if simplified pro-
gramming mode is selected.
Unit of measurement: Number step
Options: 1...192 if S.PROG = OFF; 16 if S.PROG = ON (“Simplified Programmer” mode)
4.8.3. ST.END - End step of the program configuration
Acronym Scrolling message Submenu Attributes
ST.END PR.STP.1 (o PR.STP.2…PR.STP.192) END STEP OF THE PROGRAM se mo-
dalità “Programmatore semplificato” disattiva; (o PR.STP.1…PR.STP.16) END
STEP OF THE PROGRAM se modalità “Programmatore semplificato” attiva)
PR.STP R W
This parameter shows and sets the current step as the last step in the program selected by the PR.NUM. parameter.
Appears only if simplified programming mode is selected.
Unit of measurement: -
Options: No = the current step is not the last in the program selected by the PR.NUM parameter
YES = the current step is the last in the program selected by the PR.NUM parameter
4.8.4. REFE – Step reference programmer
Acronym Scrolling message Submenu Attributes
rEFE REFERENCE PROGRAMMER PR.STP R W
The parameter shows and sets the step reference programmer.
Unit of measurement: Step number
Options: BOTH = Entrambi I programmatori
PROG1 = Programmer 1 only
PROG2 = Programmer 2 only
4.8.5. SETP - Programming step setpoint
Acronym Scrolling message Submenu Attributes
SETP PR.STP.1 (o PR.STP.2…PR.STP.192) SETPOINT se modalità“Programmatore
semplificato”disattiva; o PR.STP.1…PR.STP.16 SETPOINT se modalità“Prog-
rammatore semplificato”attiva.
PR.STP R W
The parameter shows and sets the setpoint for the current programming step.
Unit of measurement: °C, °F, % based on chosen scale
Options: -1999...9999