EasyManuals Logo
Home>gefran>Temperature Controller>850

gefran 850 User Manual

gefran 850
286 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #91 background imageLoading...
Page #91 background image
80209C_MHW_850-1650-1850_02-2020_ENG_pag. 89
TYPE 3
20MA = Sensor 0...20 mA
4-20M = Sensor 4...20 mA
10V = Sensor 0...10 V
2-10V = Sensor 2...10 V
5V = Sensor 0...5 V
1-5V = Sensor 1...5 V
2.4VHI = Sensor 0…2.4V high impedance
1.2VHI = Sensor 0…1.2V high impedance
1VHI = Sensor 0…1V high impedance
C.20MA = Sensor 0...20 mA with custom calibration
C.4-20 = Sensor 4...20 mA with custom calibration
C.10V = Sensor 0...10 V with custom calibration
C.2-10 = Sensor 2...10 V with custom calibration
C.5V = Sensor 0...5 V with custom calibration
C.1-5V = Sensor 1...5 V with custom calibration
C2.4VH = Sensor 0...2.4 V high impedance with custom calibration
C1.2VH = Sensor 0...1.2 V high impedance with custom calibration
4.9.4. SBR.E - Enabling SBR error
Acronym Scrolling message Submenu Attributes
SBR.E INPUT.1 (or INPUT.2) SBR ENABLE INPUT R W
Enables open thermocouple probe error detection, also permitting infrared sensor management with maximum 4Kohm
output impedance.
This parameter only appears when a thermocouple type input is selected.
When OFF, the parameter will be forced to ON (see options) at each Power On
Unit of measurement: -
Options: OFF = Disable SBR alarm
On = Enable SBR alarm
On.t = Enable SBR alarm with timing

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran 850 and is the answer not in the manual?

gefran 850 Specifications

General IconGeneral
Brandgefran
Model850
CategoryTemperature Controller
LanguageEnglish

Related product manuals