FX3U Series Programmable Controllers
User’s Manual - Hardware Edition
160
9 Preparation for Wiring and Power Supply Wiring Procedures
9.5 Examples of External Wiring [AC Power Supply Type]
9.5.4 An external wiring example for the extension power supply unit (sink input [-common])
This example shows a sink input wiring (-common),including the extension power supply unit.When adding an
input extension block,check the signal name on the terminal block since the sink/source type and sink type
differ from each ther.
AC power supply of
100 to 240V
*1 Connect the AC power supply to the L and N terminals (in any case of 100V
AC system and 200V AC system).
Make sure that the power is turned ON at the same time in the main unit
and extension power supply units or earlier in extension power supply units
than the main unit.
As for the details, see "WIRING PRECAUTIONS" at "Safety Precautions"
field.
*2 Connect the 24V terminal of the main unit to the S/S terminal of the input
extension block.
*3 In the case of the sink input type, the S/S terminal is used as the 24+
terminal.
*4 Some special function units/blocks do not have the power supply terminal.
When using an external power supply, turn it ON at the same time with the
main unit or earlier than the main unit.
When turning OFF the power, confirm the
safety of the system, and then turn OFF the
power of the PLC (including special
extension equipment) at the same time.
*5 Some special function units/blocks do not
have the power supply terminals.
When using an external power supply, turn it
ON at the same time with the extension
power supply unit or earlier than the
extension power supply unit.
When turning OFF the power, confirm the
safety of the system, and then turn OFF the
power of the PLC (including special
extension equipment) at the same time.
S/S
L
N
0V
Special adapter
24-
24+
Class D
grounding
PL
Power supply ON
Emergency
stop
MC
MC
MC MC
DC
power
supply
Power supply for loads to
be connected to PLC
output terminals
As for the details of emergency stop
operation, see "DESIGN
PRECAUTIONS" at "Safety Precautions"
field.
24V
Main unit
Input extension
block
S/S
24V DC
service
power
supply
output
Class D
grounding
DC AC
*1
Sink and source input type
*2,3
5V 0V 24V
5V 0V 24V
5V 0V 24V
Sink and
source
input
type
Breaker
24-
24+
Class D
grounding
*4
Special function
block
5V 0V 24V
L
N
S/S
Class D
grounding
Class D
grounding
*2,3
*1
*5
Extension power supply unit
5V 0V 24V
5V 0V 24V
Special function
block
Input extension
block
5V 0V 24V
5V 0V 24V
Output extension
block
24-
24+
Sink and
source
input
type
Wiring precaution:
Grounding and power cables should be positioned
to exit the unit from above as shown in the figure.
Grounding and
power cables

Table of Contents

Other manuals for Mitsubishi FX3U Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U Series and is the answer not in the manual?

Mitsubishi FX3U Series Specifications

General IconGeneral
BrandMitsubishi
ModelFX3U Series
CategoryController
LanguageEnglish

Related product manuals