426
FX3U Series Programmable Controllers
User’s Manual - Hardware Edition
20 FX-16/32E*-*-TB (Terminal Block)
20.8 FX-16EYT-TB, FX-16EYT-H-TB
20.8.4 External wiring precautions
1. Protection circuit for load short-circuits
A short-circuit at a load connected to an output terminal
could cause burnout at the output element or the PCB. To
prevent this, a protection fuse should be inserted at the
output. Use a load power supply capacity that is at least 2
times larger than the total rated fuse capacity.
2. Transistor protection circuit for inductive loads
The transistor output circuit in the terminal block is
equipped with a Zener diode (50V) for protection. When
an inductive load is connected, however, a diode should
be connected parallel to the load when required. The
diode must comply with the specifications shown below.
3. Interlock
For loads such as forward/reverse contactors, etc., where
a hazardous condition could result if switched ON
simultaneously, an external interlock should be provided
for interlocking the PLC’s internal programs as shown to
the right.
Counter voltage 5 to 10 times of the load voltage
Forward current Load current or more
Terminal block
0 to 7
COMn
Load
Fuse
Terminal block
0 to 7
COMn
inductive
load
Fuse
Forward
limit Interlock
Reverse
limit
PLC output
element

Table of Contents

Other manuals for Mitsubishi FX3U Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U Series and is the answer not in the manual?

Mitsubishi FX3U Series Specifications

General IconGeneral
BrandMitsubishi
ModelFX3U Series
CategoryController
LanguageEnglish

Related product manuals