The FX-16EYS-TB is used by connecting it to the FX2N series output extension block (transistor).
The applications shown below are not supported.
20.9.1 Specifications
*1. In systems where frequent large-load ON/OFF switching occurs due to rush currents, the root mean square
current should be 0.2 A or less.
*2. This response time does not include the response delay at the PLC.
Output Connector
Connectable models FX
2N-16EYT-C (sink output)
Unsupported Applications
Pulse
outputs
Pulse Y output (PLSY) instruction, acceleration/deceleration setup (PLSR) instruction, pulse width
modulation (PWM) instruction, DOG search zero return (DSZR) instruction, interruption positioning
(DVIT) instruction, batch data positioning mode (TBL) instruction, absolute current value read (ABS)
instruction, zero return (ZRN) instruction, variable speed pulse output (PLSV) instruction, drive to
increment (DRVI) instruction, drive to absolute (DRVA) instruction
Time division
inputs
Input matrix (MTR) instruction, hexadecimal input (HKY) instruction, digital switch (DSW) instruction,
arrow switch (ARWS) instruction
Time division
outputs
Seven segment with latch (SEGL) instruction, print (ASCII Code) (PR) instruction
Item TRIAC output
Input/output
circuitry
Load voltage 85 to 242V AC
Max.
load
Resistance
load
0.3 A / point
*1
The total load current of resistance loads per common terminal should be the
following value.
• 4 output points/common terminal: 0.8A or less
Inductive
load
15 VA / 100V AC
36 VA / 200V AC
Min. load
0.4 VA / 100V AC
1.6 VA / 200V AC
Open-circuit
leakage current
1 mA / 100V AC
2 mA / 200V AC
Response time
*2
2 ms or less
Circuit isolation Photocoupler isolation
Operation indicator LED lights when photo-thyristor power is supplied
Power
consumption
2.7 W (112 mA 24V DC)
0 to 7
COMn
Photo-
thyristor
External wiring
CN1
connector
side
3.3k
Ω
LED
2.2
Ω
0.015
µ
F
7mA Fuse
U
24+
0.4A
0.7
sec
4A
10
sec
0.02
sec
0.02 + 0.7 + 10
4
2
0.02 + 0.4
2
0.7
= 0.2A
<Example>