—————— TPD32-EV ——————
140
6.1.2 Start / Stop
DRIVE STATUS
START UP
TUNING
MONITOR
[315] Start/Stop
Parameter description No.
Value
Standard
Conguration
min max
Factory
American
Factory
Standard
Start/Stop
Start
Stop
315 0 1 Stop(0) Stop(0) Terminal13
+15...30V
0V
WhenMain commands issettodigital,Start/Stop parameterallowsthemotorrunningandtheSTOPbutton
onthekeypadstopthemotor.
WhenMain commands issettoterminals, Start/stopwillbeareadonlyparameter.
note! ThefollowingsignalsarerequiredforoperatingthedriveinadditiontotheStart command:
Enable drive
Fast stop
External fault
ThebehaviorofthedriveaftertheStart commandisgivenorremoveddependsontheparametersettingathand:
- Whenusingtheramp(Enable ramp=EnabledandEnable spd reg=Enabled)thedriveacceleratesto
therequiredspeedaccordingtotherampspecied.IftheStartcommandisremoved,thedriverunsdown
tozeroaccordingtotherampdened.IftheStartcommandisselectedoncemoreduringthedeceleration
time,thedriveacceleratesoncemoretotherequiredspeed.
- IftheSpeed ref 1valuereachestheinputofthespeedregulatordirectlywithoutaramp(Enable ramp =
DisabledandEnable spd reg=Enabled),thedriveacceleratestotherequiredspeedintheshortestpossible
timeoncetheStartcommandhasbeengiven.WhentheStartcommandisremoved,theSpeed ref 1value
issettozeroimmediately.
ThecommandhasnoteffectonSpeed ref 2.
- Whenusingtorqueregulation(Enable spd reg=Disabled)theStart commandenablesthetorquereference
value(T current ref 1)ordisablesitaftertheStartcommandisremoved.
TheStartcommandhasnoeffectonthecorrectionvalueSpeed ref 2(withspeedregulation)orTorque ref 2
(withtorqueregulation).
TheStartcommandisnotrequiredforJogfunctionmode.
IftheStartcommandandJog + or Jog -aregivenatthesametime,theStartcommandisgivenpriority.
IftheStartcommandisgivenduringJogoperation,theJogoperationisaborted.
TheStartparameterstatusisshownintheDRIVESTATUSandMONITORmenu.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran TPD32-EV-...-4B and is the answer not in the manual?

gefran TPD32-EV-...-4B Specifications

General IconGeneral
Brandgefran
ModelTPD32-EV-...-4B
CategoryDC Drives
LanguageEnglish

Related product manuals