—————— TPD32-EV ——————
60
3 - INSTALLATION GUIDELINES
3.1 PERMISSIBLE AMBIENT CONDITION
Protectiondegree: IP20(TypeA-B-C-D)atoperatingtemperaturesof32-131°F(0...55°C;IP00
(TypeE).
ULenclosuretype1.
(Americansize)Theconvertermustbeinstalledinapollutiondegree2environ-
ment.
Installationlocation Pollutiondegree2orlower(freefromdirectsunligth,vibration,dust,corrosive
orinammablegases,fog,vapouroilanddrippedwater,avoidsalineenviron-
ment)
Altitude: Upto3300feet(1000m)abovesealevel;higheraltitudesacurrentreduction
of1.2%forevery330feet(100m)ofadditionalaltitude.Max2000m(6562
feet)abovesealevel.
Temperature: Operation TPD32-EV-....: Ta=32-131°F(0...55°C),
over104°F(40°C):currentreduc-
tionof1.25%forevery1.8°Fove
r104°F(1°Cover40°C)betterthanthe
3K3classperEN50178)
TPD32-EV-CU-....: Ta = 0... 55 °C above
122°F(50°C)
reducethecurrentof
1.25%foreveryKabove
104°F(40°C)
(bestinclass3K3accordingtoEN
50178).
Storage Ta=-13°F...131°F(-25...+55°C)(1K4classasperEN50178)
Ta=-4°F...131°F(-20...+55°C)(fordeviceswithLCD)
Transport Ta=-13°F...131°F(-25...+55°C)(2K3classasperEN50178)
Ta=
-4°F...140°F(-20...+60°C)
(fordeviceswithLCD)
Airhumidity:
Operation 5%
upto
85%,1g/m
3
upto
25g/m
3
withoutmoisturecondensationoricing
(3K3classasperEN50178)
Storage 5%
upto
95%,1g/m
3
upto
29g/m
3
(1K3classasperEN50178)
Transport 95%
1)
,60g/m
2)
Alightcondensationofmoisturemayoccurforashorttimeoccasionallywhen
thedeviceisnotinoperation(2K3classasperEN50178).
Airpressure: Operation From86kPa
upto
106kPa(3K3classperEN50178)
Storage From86kPa
upto
106kPa(1K4classperEN50178)
Transport From70kPa
upto
106kPa(2K3classperEN50178)
1)
Greatestrelativeairhumidityoccurswiththetemperature104°F(40°C)orifthetemperatureofthedevice
isbroughtimmediatelyfrom-13°F...86°F(-25°Cto+30°C).