—————— TPD32-EV ——————
186
6.11.3 Configuration of the OK relay (Terminals 35,36)
CONFIGURATION
[412] Okrelayfunct
Parameter description No.
Value
Standard
Conguration
min max
Factory
American
Factory
Standard
Ok relay funct
Drivehealthy(0)
ReadytoStart(1)
412 0 1 0 0
-
Ok relay func Thisparameterdenestheconditioninwhichtherelaycontactwillclose.
Drivehealthy Thecontactwillclosewhenthedriveissuppliedwithvoltage
andwhentherearenofailurealarmsor“warning”settostop
themotor.Standardwarningwillnotopentherelay.
note: Therelaywillopenifmulti-warningareactiveandIPA9287Warning Cfg parameterisset
to1“Stop/NoStart”(Inthiscase,themotorwillbestoppedtoo).Incaseof“warning”when
driveisdisabled,OKRelaywillbeopenonlyifIPA9287Warning Cfg parameterissetto
4“NoStop/Start”or1“Stop/NoStart.
Readytostart Thecontactcloses whenthefollowingconditions areful-
lled:
-Thedrivehasavoltagesupply
-Therearenofailurealarmspresent
-ThedriveisenabledwithEnable drive.