—————— Instruction manual ——————
497
A2.6 Programmable alarms
CONFIGURATION
Prog alarms
SSC error
[9080] Holdofftime[ms]
Parameter No. Format
Value Access via
min max Factory Keyp.
RS485/
BUS/
Opt2-M
Term.
Opt2-A/
PDC
Holdofftime[ms]
9080 U16 0 500 80
ü
R/W - -
Alarm N.
Factory
Standard
Activity Latch Open
OK relay
Hold off
time [ms]
Restart
time [ms]
SSC error
Disabledrive - - 80 -
Alarm Ignore Warning Disable drive Quick stop Normal stop Curr lim stop
SSC error
- - X - - -
SSC error FunctionalityavailablestartingfromFirmwareTPD32-EV-FC10.25A(FC-200V)and
10.26A(FC-500V).
Hold off time parameter.:ItisneededtogenerateaSSCalarmifthedrivedoesnotreceive
inthetimeframesetavaliddatathrutheopticalber.
Thealarmdoesnotcausereactionofthedrive.Awarningmessagecanbeoutputvia
adigitaloutput.Whenthedriveisdisabled,itwillnotrestartuntilthefailurehasbeen
cancelled.
Ifthefailureisnomoreactive,thedrivecanberesetwithoutstoppingthemotor.