—————— Instruction manual ——————
193
6.11.6 “Standard / American” selection, Software Version
CONFIGURATION
Drive type
[465] Drivesize[A]
[201] 2B+E
[464] Sizeselection
[331] Softwareversion
Parameter description No.
Value
Standard
Conguration
min max
Factory
American
Factory
Standard
Drive size [A]
465 0 S S S -
2B + E
ON(Off)(0)
OFF(On)(1)
201 0 1 0 0 -
Size selection
Standard(0)
American(1)
464 0 1 1 0 -
Software version
331 -
Drive type
TPD32-EV-...-2B
TPD32-EV-...-4B
300 10 11 S S -
Drive size Displayoftheconverterarmaturecurrentinampere(itiscodiedbytheSW15Switch
placedontheR-TPD32-EVregulationcard).Thestatedvaluedependsonthesetting
oftheSize selection parameter.
2B + E Selectionofthe2B+externalexcitationconguration.Onlyfor2Bconverters.The
functionallowsthedrivetoworkwithanexternal4quadranteldcontroller.When
theparameterisOntheRamp/Speed/TcurrentreferencesandSpeedmeasurement
havethesamebehaviourofthe4Bdrive.
Size selection Withthe“Standard”selectiontheconverterproducesratedcurrentinacontinuative
wayinthepresetambientconditionswithoutoverload(foroverloadsee6.14.5).With
“America”selectiontheratedcurrentisdenedconsideringanoverloadof1.5timesfor
60seconds.Thiscausesareductionoftheconverterratedcurrent(continuativecurrent)
forthesametypeofdrive.Seesection4.4,R-TPD32-EVRegulationcard.
Standard Theconverterproducesratedcurrentinacontinuativeway.
ItisstatedasDrive size.Nooverloadfunctionsareset.
American Theratedcurrent(producedcontinuously)willbereducedto
thevaluestatedinthementionedtableandindicatedinFull
load currentandDrive size parameters.
Automatically,theoverloadfunction(FUNCTION\Overload
control),issettothefollowing:
Enable overload=ON Overload mode=I2tmotor
Overload time=60s
Full load current=American
Pause time=540s T current lim=150%
Overload current=150% T current lim+=150%
Base current=100% T current lim -=150%
Ifthesize“American”isselected,theparameterOvercurrent thr[584]willbesetat160%
note! Iftheconverterisreconguredas“Standard”,theseparametersandthecontinuouscurrent
limittakethevaluescorrespondingtothepreviousconguration(overloaddisabled)andthe
parameterOvercurrent thr [584]returnsto110%.
Software version Displayofthesoftwareversionnumberactiveintheconverter.
Drive type Displayofthedrivetype:2Bor4B.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the gefran TPD32-EV-...-4B and is the answer not in the manual?

gefran TPD32-EV-...-4B Specifications

General IconGeneral
Brandgefran
ModelTPD32-EV-...-4B
CategoryDC Drives
LanguageEnglish

Related product manuals