313
FX3UC Series Programmable Controllers
User’s Manual - Hardware Edition
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
9.18 Details of buffer memory
1
Outline
2
External
Dimensions
3
Generic
Specifications
4
Power Supply
Specifications
5
Input
Specifications
6
Output
Specifications
7
Examples of
Wiring for
Various Uses
8
Terminal Block
9
CC-Link/LT
Master FX
3UC
(LT only)
10
Display module
FX
3UC
(LT only)
9.18.9 Command [BFM #27 (1Bh)]
The command BFM gives the built-in master instructions to stop/restart the data link and write data to the
EEPROM.
1. Detailed description
A function is assigned to each bit of the buffer memory [BFM #27 (1Bh)]. Each function is executed according
to the 0 (OFF)/1 (ON) status of each bit.
1) Request to write to EEPROM (b4)
When this bit is set to ON, the contents of the detailed remote station information [BFM #32 (20h) to #95
(5Fh)] are written to the built-in EEPROM.
This write is unnecessary when reserved stations are not specified or when the detailed remote station
information is not edited.
The operation is as shown below.
2) Request to stop data link (b5)
Data link is stopped when this bit [BFM #27 (1Bh) b5] is set to ON while the data link is being executed.
The data link is restarted when this bit is set to OFF.
The operation is as shown below.
Bit Function Description
b0 to b3 - Prohibited to use
b4
Request to write to the
EEPROM
Writes the contents of the detailed remote station information [BFM #32 (20h)
to #95 (5Fh)] stored in the buffer memory to the built-in EEPROM when it is set
from OFF to ON.
After the write to the EEPROM is completed (completion is indicated when b4
of BFM #28 turns ON), set this bit to OFF.
b5 Request to stop data link
Stops data link when set from OFF to ON.
Restarts data link when set from ON to OFF.
b15 to b6 - Prohibited to use
Data is being written to the
EEPROM.
Set the write request flag to OFF after completion
of the write is confirmed.The write completion flag
turns OFF automatically.
Request to write EEPROM
[BFM #27 (1Bh) b4]
EEPROM write completion
[BFM #28 (1Ch) b4]
The L RUN is extinguished.
Request to stop data link
[BFM #27(1Bh) b5]
Data link stopped
[BFM #28(1Ch) b5]
The link is stopped. The link is restarted.
L RUN

Table of Contents

Other manuals for Mitsubishi FX3UC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3UC Series and is the answer not in the manual?

Mitsubishi FX3UC Series Specifications

General IconGeneral
BrandMitsubishi
ModelFX3UC Series
CategoryController
LanguageEnglish

Related product manuals