FX3UC Series Programmable Controllers
User’s Manual - Hardware Edition
1 Outline
1.14 Selection Calculation Example 3 for System Configuration
1.14.1 Judgment of availability after reexamination of configuration
In this configuration, it is necessary to add an extension power supply unit FX3UC-1PS-5V due to the
restrictions in the 5V DC power supply capacity and the restriction in the number of connectable units.
Construct the system as follows.
1. Example of reexamined system configuration
Insert an extension power supply unit FX3UC-1PS-5V between the FX2NC-16EYR-T and the FX2NC-16EYR-
T.
2. Reexamination of system configuration availability
1) Restriction for the number of input/output points
There is no problem since the number of input/output points in the new system is "208".
2) Restriction for the 5V DC power supply capacity
The 5V DC power supply capacity is as follows after countermeasures.
- Main unit side
CC-Link/LT
CL1X4-D1B2
4 points, input units
(Station No.1, Number
of occupied stations 1)
AJ65BTB1-16T
16 points input units
(Remote I/O station)
AJ65BTB1-16D
16 points input units
(Remote I/O station)
OK!!
FX
3U
-
4AD-ADP
FX
3U
-
485-ADP
(-MB)
FX
3U
-
232-BD
FX
2NC
-
32EX
FX
2NC
-
32EYT
FX
2NC
-
16EYR-T
FX
2NC
-
16EYR-T
FX
2NC
-
4AD
FX
2NC
-
CNV-IF
FX
2N
-
10PG
FX
2N
-
2LC
FX
2N
-
16CCL-M
FX
3UC
-
32MT-
LT
FX
3UC
-
1PS-5V
Terminating resistor
Terminating
resistor
Terminating
resistor
Terminating
resistor
CL1Y4-T1B2
4 points, output units
(Station No.2, Number
of occupied stations 1)
a)Supplier side
FX
3UC
-32MT-LT 350mA
b)Consumer side
FX
3U
-232-BD
FX
2NC
-32EX
FX
2NC
-32EYT
FX
3U
-4AD-ADP
20mA
60mA
100mA
15mA
50mAFX
2NC
-16EYR-T
40mA
55mA
115mA
215mA
265mA
5V DC power supply capacity and current consumption
FX
3U
-485ADP(-MB) 20mA
"a)Supplier side" - "b)Consumer side" = 350mA - 265mA = 85mA
0mA
There is no problem since the total current consumption is less than the
capacity "350mA" supplied by the main unit.
OK!!

Table of Contents

Other manuals for Mitsubishi FX3UC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3UC Series and is the answer not in the manual?

Mitsubishi FX3UC Series Specifications

General IconGeneral
BrandMitsubishi
ModelFX3UC Series
CategoryController
LanguageEnglish

Related product manuals