421
FX3UC Series Programmable Controllers
User’s Manual - Hardware Edition
B Performance Specifications
11
Memory
Cassette/Battery
12
Test Run,
Maintenance,
Troubleshooting
A
Version
Information
B
Performance
Specifications
C
Special Devices
(M8000 -,D8000 -)
D
Instruction List
E
Character-code
F
Discontinued
models
Appendix B: Performance Specifications
For the built-in CC-Link/LT master ability and network specifications, refer to Section 9.2.
*1. Supports the FX
3UC-32MT-LT.
Item Performance
Operation control system
Stored program repetitive operation system (dedicated LSI) with
interruption function
I/O control system
Batch processing system (when END instruction is executed)
Input/output refresh instruction and pulse catch function are provided.
Programming language Relay symbol system + step-ladder system (SFC notation possible)
Program
memory
Max. memory capacity
64000-step (2k-, 4k-, 8k-, 16k- or 32k-step memory can be selected by
parameter settings.)
Comments and file registers can be created in the program memory by
parameter settings.
• Comments: Up to 6350 points (50 points/500 steps)
• File registers: Up to 7000 points (500 points/500 steps)
Built-in memory
capacity/type
64000-step RAM (backed up by built-in lithium battery)
• Battery life: Approx. 5 years (guarantee for 1 year)
• With password protection function (with entry code function)
Memory cassette
(Option)
Ver.2.20 or later
Flash memory
(The max. memory capacity varies depending on the model of the
memory cassette.)
•FX
3U-FLROM-64L:64000 steps (with loader function)
•FX
3U-FLROM-64: 64000 steps (without loader function)
•FX
3U-FLROM-16: 16000 steps (without loader function)
Max. allowable write: 10,000 times
Former than Ver. 2.20
Flash memory
•FX
3U-FLROM-64: 64000 steps (without loader function)
Max. allowable write: 10,000 times
Writing function during
running
Provided (Program can be modified while the PLC is running.)
Display
Module
*1
Display device STN monochrome liquid crystal display, Backlight: LED (green)
Displayed letters
16 letters × 4 lines, 2 byte letters: 8 letters × 4 lines
Japanese Characters (Shift JIS Level-1, 2), English Alphabet
Language for menu display: Japanese/English
Function
Monitor / Test, User-registered monitor, Error Check,
PLC Status (Error,
Program memory type status
,
Battery voltage,
Main unit I/O operation display), User message display
Real-time
clock
Clock function
Built-in
1980 to 2079 (with correction for leap year)
2- or 4-digit year, accuracy within ±45 seconds/month at 25°C
Kinds of
instructions
Basic instructions
Ver.2.30 or later
• Sequence instructions: 29
• Step-ladder instructions: 2
Former than Ver.2.30
• Sequence instructions: 27
• Step-ladder instructions: 2
Applied instructions
Ver.2.20 or later
• 209 kinds 486 instructions
Former than Ver.2.20
• 181 kinds 407 instructions