– After the rst login, change the preset password in time to ensure system access
security.
– A password that has been used for a long time is more likely to be stolen or cracked.
The risk increases over time. Change the password once every three months.
– It is recommended that you use
dierent user accounts to log in to the ECC800-Pro
WebUI and app concurrently. Otherwise, either of them will be logged out.
----End
5.3.3 (Optional) Cloud Service Access
The ECC can connect to the NetEco only after NetEco communications parameters
are set on the ECC WebUI.
Prerequisites
● You have obtained the IP address of the ECC as well as the user name and
password used for WebUI login.
Procedure
Step 1 Enter https://monitoring IP address (such as https://192.168.1.10) in the
address box of the browser, and then press Enter to enter the WebUI login page.
Step 2 On the login page, enter the user name and password, select a language, and click
Log In.
● If you do not perform any operation within 10 minutes after logging in to the system,
you will be logged out due to timeout.
● A maximum of three users can log in to the ECC WebUI concurrently.
Step 3 Set parameters.
1. Existing sites:
a. Choose System Settings > System Parameters. In the Mobile Data area
in the right pane, change Disable of Mobile data control to Enable.
b. If the domain name access mode is used, click the Monitor IP tab in the
right pane, and enter the DNS server address.
c. Choose System Settings > NMS Application. On the NetEco tab page,
set parameters in the Communication Parameters area, such as Address
type, NetEco domain name, Port number, and Network port for link
setup, and click Submit.
d. After setting the parameters, check whether the dial-up connection is
successful. Choose Home > Mobile Data Info., and check whether the
dial-up connection is set up successfully and check the signal strength.
2. New sites:
a. The startup password is displayed on the ECC WebUI. After the
verication is successful, the cloud service access page is displayed.
b. Select the 4G cloud access to enter the wizard. In the second step of the
wizard, the NetEco communications parameters are hidden. Check that
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 183