2.3 Field Requirements
To prevent condensation, a
dehumidier must be installed in the equipment room
when the dew point temperature is higher than 18°C (temperature: 18°C,
humidity: 100% RH; temperature: 27°C, humidity: 57% RH).
● The cabinet layouts shown in the gures are for ease of description and do not provide
reference for engineering layout.
● The cold and hot aisle containment of nine standard cabinets is used as an example in
this document, which supports a maximum deployment of 24 IT cabinets.
● If the site conditions do not meet the
eld requirements, contact technical support.
Figure 2-1 Space requirements for a simplied single-row MDC
FusionModule2000-S Smart Modular Data Center
User Manual 2 Installation Preparations