2.3 Field Requirements
NO TICE
To prevent condensation, a
dehumidier must be installed in the equipment room
when the dew point temperature is higher than 18°C (temperature: 18°C,
humidity: 100% RH; temperature: 27°C, humidity: 57% RH).
NO TE
The cabinet layouts shown in the gures are for ease of description and do not provide
reference for engineering layout.
The cold and hot aisle containment of nine standard cabinets is used as an example in
this document, which supports a maximum deployment of 24 IT cabinets.
If the site conditions do not meet the
eld requirements, contact technical support.
Figure 2-1 Space requirements for a simplied single-row MDC
FusionModule2000-S Smart Modular Data Center
User Manual 2 Installation Preparations
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 30